Thursday Apr 25 2024

T & T Inspection And Engineering Sdn Bhd

You are here Field Power Solution

Power Solution

Major Track Record On Power Quality and Engineering Project

1) Airport Conveyor System – Fibre Optic Converter Frequent Failure Issue

2) Airport Runway Lighting CCR Panel Frequent Fuse Blown Issue

3) DC Traction Railway System Power System Stability Study

4) Copper Plant UPS System nuisance Tripping Issue

5) Steel Mill Plant – Harmonics Contents Study and Analysis

6) Automotive Plant – CNC Machine Control System Frequent Failure Issue

7) Double Traction Railway System – Booster Transformer On Transmission Line Lighting Arrester Frequent Failure Issue

8) Semiconductor Plant Neutral System Voltage Issue

9) Electronics Plant – Power Quality Audit and Analysis


Complete Power Quality & Engineering Study

1. Complete System Inspection

2. Earthing/Grounding System Inspection

3. Component/Sub-System/Equipment Analysis & Inspection

4. Full Power Quality System Analysis And Study

  • a) Energy And Demand Study
  • b) Load Study
  • c) Power Study (Voltage And Current)
  • d) Power Factor/Frequency
  • e) Harmonics
  • f) Flickers
  • g) Voltage Unbalance
  • h) Voltage Sag
  • i) Voltage Swell
  • j) Voltage Transient

Detail Description On The PQ Specification

Load Studies & Energy Demand Interactions

The parameters that will be recorded are kW demand, kVA demand, kVAR demand and maximum demand throughout the durations of the measurement.

The readings recorded are of average value. The logging interval in this case is at 15 minutes and sampling at every 1 second – Can be customized depends on requirement & specification in the study and analysis input requirement.

Results at the end of the measurement can be peak, minimum and maximum and average of the parameters.

The below graph will be obtained.

Load Studies & Energy Demand Interactions


Power Study

The parameters that will be recorded are Voltage and Current RMS value for each individual phase throughout the durations of the measurement.

The readings recorded are of average value. The logging interval in this case is at 15 minutes and sampling at every 1 second - Can be customized depends on requirement & specification in the study and analysis input requirement.


Power Factor & Frequency

The leading/lagging of the power factor for all the phases will be logged at every 10 minutes at the sampling of every 1 second – Can be customized depends on requirement & specification in the study and analysis input requirement.


Flickers

Flickers will be captured and calculated according to the IEC 6100-4-15 with build in pass/fail indications together with the index of the flickers. This flicker indexes will be logged at every 10 minutes – Can be customized depends on requirement & specification in the study and analysis input requirement.

Flickers


Harmonics

The THD and individual harmonics up to 63th will be sampled and logged

Right after, Voltage and Current THD for all phases will be logged at every 10 minutes at the sampling rate of 1 second – Can be customized depends on requirement & specification in the study and analysis input requirement.

Harmonics


Voltage Sag/Swell

The threshold of the voltage sag is recommended to be set at 90% and swell to be set at 110%. The Threshold value can be reset to melt the PQ Study requirement and local statutory requirement and standard.

The result of the above capturing are the magnitude, duration, timestamp and the waveform of the sags or swells.


Voltage Transient

Detect and record as fast as 17us up to half a cycle. The threshold for transient is set at 125% of the nominal. It will capture the voltage surge as transient when it happens between 0-10ms time and the magnitude is shooting up more than 125%.


Unbalance voltage

WHETHER YOU CALL IT "unbalance" (the NEMA standard term) or "imbalance," equality of all three phase voltages is the basis for design and rating of three phase systems and apparatus, including motors.

The value of the voltage unbalance is logged at every 10 minutes at the sampling of 1 second. The unit of the voltage unbalance is set at % – Can be customized depends on requirement & specification in the study and analysis input requirement.

 

Contact Us

Go To Top